Srm6000/6100/6200e-plc -27 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 293

Publication AG-UM008C-EN-P - February 2005
Configuring Modems 8-27
Data connection for the SRM6200E-SLC is via a RJ45 10BAST-T
Ethernet port.
The SRM6000/6100/6200E-SLC are pre-configured. Use the
SRM6000/6100/6200E-SLC User’s Guide (available from DATA-LINC) to
change configuration in the field.
SRM6000/6100/6200E-PLC
The DATA-LINC SRM6000/6100/6200E-PLC are license-free, spread
spectrum frequency-hopping wireless modem that fits directly into the
Allen-Bradley PLC-5 chassis. The modems can be configured as
master, remote, or repeater (SRM6000/6100-PLC only), and data
communications are asynchronous. Baud rates can be set as high as
115.2K.
To connect the SRM6000-PLC or SRM6100-PLC to a PLC-5, use the
DATA-LINC communication cable part number C232/SRM60/PLC5/CH
0, CABLE ASSEMBLY SRM6000 to Allen-Bradley PLC-5.
The modem pin assignment is as follows:
Table 8.24 SRM6000-PLC and SRM6100-PLC Pin Assignment
SRM6000 Pin #
PLC-5 25-Pin
Assignment
1
8
Carrier Detect
2
3
Transmit Data
3
2
Receive Data
4
20
DTR
5
7
Signal Ground
6
6
DSR
7
4
RTS
8
5
CTS
9
NC
Ground