Installing the controller – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 229

Publication AG-UM008C-EN-P - February 2005
Configuring Logix Controllers 7-3
Installing the Controller
For details about installing the controller, see the Logix Controller
Installation Instructions.
For cable pin assignments, see below, or page A-5.
Figure 7.2 Logix Serial Port Pin Assignments
Using Modems that Support
DF1 Communication
Protocols
The types of modems that you can use with Logix controllers include
dial-up phone modems, leased-line modems, radio modems and line
drivers. For point-to-point full-duplex modem connections, use DF1
full-duplex protocol. For point-to-multipoint modem connections, use
DF1 half-duplex master and slave protocols. In this case, one (and
only one) of the other devices must be configured for DF1 half-duplex
master protocol.
9-pin female
25-pin Modem
9-pin Modem
DCD.IN
1
8
1
RXD.IN
2
3
2
TXD.OUT
3
2
3
DTR.OUT
4
20
4
SIG.GND
5
7
5
DSR.IN
6
6
6
RTS.OUT
7
4
7
CTS.IN
8
5
8
RS-232
I/O
RUN
OK
RUN
REM
PROG
BAT
9-pin female cable connector
to modem