3-68 Configuring MicroLogix 1100/1200/1500 Controllers
Information for Creating Your Own Application
Controller Receives Communications Packet
Table 3.14 Command Structure
DST
SRC
CMD 0f
STS
TNS
FNC A2
Byte Size
File No.
File Tpe
Ele. No.
S/Ele. No.
Field
Function
Description
DST
Destination Node
SRC
Source Node
CMD
Command Code
STS
Status Code
Set to zero (0)
TNS
Transaction Number
Always 2 bytes
FNC
Function Code
Byte Size
Number of bytes to be read
Formatted string length (see equation below)
File Number
Always set to zero (0)
File Type
Must be A5 (hex)
Element Number
Queue number
Determines the queue to be read (0 to 255)
Sub/Element Number
Always set to zero (0)
Table 3.15 Equation
Record Field 1 + Record Field 2 + Record Field 3 … + Record Field 7
= Formatted
String Length
Table 3.16 Record Field Sizes
Data Type
Maximum Size
Word
7 bytes (characters)
Long Word
12 bytes (characters)
Date Field
11 bytes (characters)
Time Field
9 bytes (characters)
TIP
The formatted string length cannot exceed 80 bytes
in length.
TIP
The last byte will be a zero value representing the
terminator character.