10 FLEX Ex Frequency Input Module

Publication

1797-5.9 - June 2010

Relay Connections

Type of Input

Channel 0 Terminations

4

Channel 1 Terminations

4

Power

Input

GND

5

Power

Input

1

GND

5

Frequency

NAMUR Proximity

1

7

6

8

9

Contact Switch

2

7

6

8

9

500 mV ac Magnetic Pickup

5

3

10

12

50 mV ac Magnetic Pickup

3

5

3

10

12

6V ac Vortex

2

1

3

13

14

12

3V ac Vortex

2

0

3

13

15

12

Gate

NAMUR Proximity

1

24

23

25

26

Contact Switch

2

24

23

25

26

500 mV ac Magnetic Pickup

22

20

27

29

50 mV ac Magnetic Pickup

3

22

20

27

29

1

As defined by standard DIN 19234.

2

Add external resistor across field device for wire-off detection (0.4 mA) - (about 15

20 K

).

3

Add a jumper between 50 mV Sel and N (frequency - channel 0 = 4

to

6, channel 1 = 9

to

11;

gate - channel 0 = 21 to 23, channel 1 = 28

to

26).

4

Connect cable shields to shield busbar or shield terminating feedthroughs.

5

All GND terminals are internally connected together.

Channel 0 Relay Connections

Channel 1 Relay Connections

COM

37

COM

46

N.O.

17

N.O.

31

N.C.

18

N.C.

32