Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual
Page 28

28 FLEX Ex Frequency Input Module
Publication
1797-5.9 - June 2010
Table 1
Table 2
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
F)
L
a
(mH)
1 and 2
Any one
channel
6, 7;
9, 8;
23, 24
26, 25
14.7
15.0
-
-
A, B
0.65
130.0
C, E
1.95
390.0
D, F, G
5.20
1040.0
1 and 2
Any one
channel
5, 3;
10, 12;
22, 20;
27, 29
14.7
10.0
-
-
A, B
0.65
300.0
C, E
1.95
900.0
D, F
5.20
2400.0
1 and 2
Any one
channel
5, 3, 6, 4;
10, 12, 9, 11;
22, 20, 21,
23;
27, 29, 26,
28
14.7
10.0
-
-
A
0.65
300.0
C, E
1.95
900.0
D, F, G
5.20
2400.0
1 and 2
Any one
channel
0, 2, 3;
1, 2, 3;
14, 12, 13;
15, 12, 13
26.5
82.0
-
-
A, B
0.13
4.5
C, E
0.39
13.5
D, F, G
1.04
36.0
Wiring
Method
Channel
Terminals
V
max
(V)
I
max
(mA)
Groups
C
i
(
F)
L
i
(mH)
1 and 2
Any one
channel
17, 18, 37
or
31, 32, 46
28
93.0
A, B
Negligible
Negligible
C, E
Negligible
Negligible
D, F, G
Negligible
Negligible
Terminals
V
t
(V)
I
t
(mA)
Groups
C
a
(
F)
L
a
(
H)
Male Bus
Connector
5.8
400
A-G
3.0
3.0