Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual

Page 28

Advertising
background image

28 FLEX Ex Frequency Input Module

Publication

1797-5.9 - June 2010

Table 1

Table 2

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(mH)

1 and 2

Any one

channel

6, 7;
9, 8;

23, 24
26, 25

14.7

15.0

-

-

A, B

0.65

130.0

C, E

1.95

390.0

D, F, G

5.20

1040.0

1 and 2

Any one

channel

5, 3;

10, 12;
22, 20;

27, 29

14.7

10.0

-

-

A, B

0.65

300.0

C, E

1.95

900.0

D, F

5.20

2400.0

1 and 2

Any one

channel

5, 3, 6, 4;

10, 12, 9, 11;

22, 20, 21,

23;

27, 29, 26,

28

14.7

10.0

-

-

A

0.65

300.0

C, E

1.95

900.0

D, F, G

5.20

2400.0

1 and 2

Any one

channel

0, 2, 3;
1, 2, 3;

14, 12, 13;

15, 12, 13

26.5

82.0

-

-

A, B

0.13

4.5

C, E

0.39

13.5

D, F, G

1.04

36.0

Wiring

Method

Channel

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

F)

L

i

(mH)

1 and 2

Any one

channel

17, 18, 37

or

31, 32, 46

28

93.0

A, B

Negligible

Negligible

C, E

Negligible

Negligible

D, F, G

Negligible

Negligible

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(

H)

Male Bus

Connector

5.8

400

A-G

3.0

3.0

Advertising