1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 1 as

required for this type of module.

Do not change the position of the keyswitch after wiring the
terminal base unit.

2. Make certain the flexbus connector (3) is pushed all the way to the left to

connect with the neighboring terminal base/adapter.

You cannot install the module unless the connector is fully
extended.

3. Make sure the pins on the bottom of the module are straight so they will

align properly with the connector in the terminal base unit.

4. Position the module (4) with its alignment bar (5) aligned with the groove

(6) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit. The

module is seated when the latching mechanism (7) is locked into the

module.

6. Make certain that you only connect terminal base units to other

intrinsically safe system modules or adapters to maintain the integrity of

the intrinsically-safe backplane.

7. Remove cap plug (8) and attach another intrinsically safe terminal base

unit to the right of this terminal base unit if required.

Installation in Zone 1

This module must not be exposed to the environment. Provide a suitable
metal enclosure. This module has a protection factor of IP20.

ATTENTION

This module cannot be used in an intrinsically safe
environment after it has been exposed to non-intrinsically
safe signals.