Ce/cenelec i/o entity parameters, Channel 0 frequency input – Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual
Page 18

18 FLEX Ex Frequency Input Module
Publication
1797-5.9 - June 2010
CE/CENELEC I/O Entity Parameters
Channel 0 Frequency Input
Field devices may only be connected to the terminals of one of the five
following circuits. The terminals of the remaining four circuits must not be
connected.
Namur/
Contact
(Terminals
6…7)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 15 mA
P
o
= 30 mW
Ex ia
IIB
3.86
F
300 mH
2.6 mH/
IIC
620 nF
80 mH
0.65 mH/
Magnetic 500 mV
(Terminals 5…3)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 10 mA
P
o
= 18 mW
Ex ia
IIB
3.86
F
600 mH
4.15 mH/
IIC
620 nF
150 mH
1.03 mH/
Magnetic 50 mV
(Terminals 5…3,
6…4)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 10 mA
P
o
= 18 mW
Ex ia
IIB
3.86
F
600 mH
4.15 mH/
IIC
620 nF
150 mH
1.03 mH/
Vortex 6V
(Terminals
1, 2…3)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 26.5V
I
o
= 82 mA
P
o
= 520 mW
Ex ia
IIB
730 nF
8 mH
0.26 mH/
IIC
95 nF
2 mH
0.06 mH/
Vortex 3V
(Terminals
0, 2…3)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 26.5V
I
o
= 82 mA
P
o
= 520 mW
Ex ia
IIB
730 nF
8 mH
0.26 mH/
IIC
95 nF
2 mH
0.06 mH/