Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual

Page 16

Advertising
background image

16 FLEX Ex Frequency Input Module

Publication

1797-5.9 - June 2010

Frequency input characteristics

Magnetic pickup: 50 mV, 500 mV
NAMUR: 8V, 8 mA
Flowmeter: low <3V, high >6V

Frequency input impedance rating

>5 k

 magnetic pickup

>10 K

flowmeter

Outputs

2 relay outputs

Output switching time

<10 ms

Gate inputs

2

Input (intrinsically safe) to DIN19234
(NAMUR)

No load voltage short
Circuit current
Switching point/
Switching hysteresis
Input pulse length/
Pulse pause
Lead breakage monitoring

8V dc/8 mA

1.2…2.1 mA/0.2 mA

>20

s/>20 s

Breakage current <0.35 mA

Indicators

6 yellow status indicators
4 red fault indicators
1 green module power indicator

Output (intrinsically safe)
(16 pin male and female Flexbus
connector)

U

o

< 5.8V

I

o

< 400 mA

L

i

< Negligible

C

i

< 2.64

F

Isolation path
Input to power supply
Input to Flexbus
Input to input
Output to power supply
Output to Flexbus
Output to output

Isolation Type
Galvanic to DIN EN 60079-11
Galvanic to DIN EN 60079-11
None
Galvanic to DIN EN 60079-11
Galvanic to DIN EN 60079-11
Galvanic to DIN EN 60079-11

Power supply
(+V, -V intrinsically safe)

U

i

< 9.5V dc

I

i

< 1 A

L

i

= Negligible

C

i

= Negligible

Module field-side power
consumption

4.25 W

Power dissipation

4.25 W

Specifications continued on next page.

Advertising