FLEX Ex Frequency Input Module 23

Publication

1797-5.9 - June 2010

Table 1

Wiring Methods

 Wiring method 1 - Each channel is wired separately.
 Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electrical Code
(NEC) or Canadian Electrical Code (CEC).

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(mH)

1 and 2

Any one

channel

6, 7;
9, 8;

23, 24
26, 25

14.7

15.0

-

-

A, B

0.62

80.0

C, E

1.82

320.0

D, F, G

4.96

640.0

1 and 2

Any one

channel

5, 3;

10, 12;
22, 20;

27, 29

14.7

10.0

-

-

A, B

0.62

150.0

C, E

1.82

600.0

D, F, G

4.96

1200.0

1 and 2

Any one

channel

5, 3, 6, 4;

10, 12, 9, 11;

22, 20, 21,
23; 27, 29,

26, 28

14.7

10.0

-

-

A, B

0.62

150.0

C, E

1.82

600.0

D, F, G

4.96

1200.0

1 and 2

Any one

channel

0, 2, 3;
1, 2, 3;

14, 12, 13;

15, 12, 13

26.5

82.0

-

-

A, B

0.095

2.0

C, E

0.285

8.0

D, F, G

0.76

16.0

Wiring

Method

Channel

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

F) L

i

(mH)

1 and 2

Any one

channel

17, 18, 37

or

31, 32, 46

28

93.0

A, B

0.0

0.0

C, E

0.0

0.0

D, F, G

0.0

0.0