Channel 1 frequency input, Flex ex frequency input module 19 publication – Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual

Page 19

Advertising
background image

FLEX Ex Frequency Input Module 19

Publication

1797-5.9 - June 2010

Channel 1 Frequency Input

Field devices may only be connected to the terminals of one of the five

following circuits. The terminals of the remaining four circuits must not be

connected.

Namur/

Contact

(Terminals

9…8)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 15 mA

P

o

= 30 mW

Ex ia

IIB

3.86

F

300 mH

2.6 mH/

IIC

620 nF

80 mH

0.65 mH/

Magnetic 500 mV

(Terminals

10…12)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10 mA

P

o

= 18 mW

Ex ia

IIB

3.86

F

600 mH

4.15 mH/

IIC

620 nF

150 mH

1.03 mH/

Magnetic 50 mV

(Terminals

10…12, 9…11)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10 mA

P

o

= 18 mW

Ex ia

IIB

3.86

F

600 mH

4.15 mH/

IIC

620 nF

150 mH

1.03 mH/

Vortex 6V

(Terminals

14, 13…12)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 26.5V

I

o

= 82 mA

P

o

= 520 mW

Ex ia

IIB

730 nF

8 mH

0.26 mH/

IIC

95 nF

2 mH

0.06 mH/

Vortex 3V

(Terminals

15, 13…12

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 26.5V

I

o

= 82 mA

P

o

= 520 mW

Ex ia

IIB

730 nF

8 mH

0.26 mH/

IIC

95 nF

2 mH

0.06 mH/

Advertising