20 FLEX Ex Frequency Input Module

Publication

1797-5.9 - June 2010

Channel 0 Gate Input

Field devices may only be connected to the terminal of one of the three

following circuits. The terminals of the remaining two circuits must not be

connected.

Namur/

Contact

(Terminals

23…24)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 15 mA

P

o

= 30 mW

Ex ia

IIB

3.86

F

300 mH

2.6 mH/

IIC

620 nF

80 mH

0.65 mH/

Magnetic 500 mV

(Terminals

22…20)

Protection

Group

Allowed

Capacitance

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10 mA

P

o

= 18 mW

Ex ia

IIB

3.86

F

600 mH

4.15 mH/

IIC

620 nF

150 mH

1.03 mH/

Magnetic 50 mV

(Terminals

22…20, 23…21)

Protectio

n

Group

Allowed

Capacitanc

e

Allowed

Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10 mA

P

o

= 18 mW

Ex ia

IIB

3.86

F

600 mH

4.15 mH/

IIC

620 nF

150 mH

1.03 mH/