Table 2



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a

system when the approved values of V

t

and I

t

of the associated apparatus are

less than or equal to V

oc

and I

sc

or V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus. The internal capacitances Ci of the terminal base must be taken

into account to verify the intrinsic safety.



Simple apparatus is defined as a device which neither generates nor

stores more than 1.2V, 0.1 A, 20 J, or 25 mW.



Wiring methods must be in accordance with the National Electrical

Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electrical Code

CSA C22.1, Part 1, Appendix F. For additional information refer to

ANSI/ISA RP12.6.



This module, 1797-IJ2, must be used with terminal base 1797-TB3 or

1797-TB3S.



Terminals 19, 30, 36, 38, 39, and 47…49 shall not be connected.



Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(

H)

Male Bus Connector

5.8

400

A-G

3.0

3.0

WARNING

Substitution of components may impair intrinsic safety

AVERTISSEMENT

La substitution de composant peut compromettre la securite
intrinseque.

IMPORTANT

For detailed certification information, refer to the FLEX Ex System
Certification Reference Manual, publication 1797-6.5.6