FLEX Ex Frequency Input Module 29

Publication

1797-5.9 - June 2010



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a

system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated

apparatus are less than or equal to V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus.



Simple apparatus is defined as a device which neither generates nor

stores more than 1.2V, 0.1 A, 20 J, or 25 mW.



Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505. For additional information refer to

ANSI/ISA RP12.6.



This module, 1797-IJ2, must be used with terminal base 1797-TB3 or

1797-TB3S.



Terminals 19, 30, 36, 38, 39, and 47…49 shall not be connected.



WARNING

Substitution of components may impair intrinsic safety

AVERTISSEMENT

La substitution de composant peut compromettre la securite
intrinseque.