Rockwell Automation 1797-IJ2 FLEX Ex Frequency Input Module User Manual

Page 17

Advertising
background image

FLEX Ex Frequency Input Module 17

Publication

1797-5.9 - June 2010

Thermal dissipation, max

14.5 BTU/hr

Module location

Cat. No. 1797-TB3 or 1797-TB3S Terminal Base Unit

Conductor wire size

4 mm

2

(12 gauge ) stranded max

1.2 mm (3/64 in.) insulation max

Dimensions,approx.

(HxWxD)

46 x 94 x 75 mm
(1.8 x 3.7 x 2.95 in.)

Weight, approx.

200 g

Keyswitch position

1

Environmental conditions

Operational temperature
Storage temperature
Relative humidity
Shock

Operating

Nonoperating

Vibration

-20…70

°

C (-4…158

°

F)

-40…85

°

C (-40…185

°

F)

5…95% noncondensing
Tested to 15 g peak acceleration, 11(+1) ms pulse width
Tested to 15 g peak acceleration, 11(+1) ms pulse width
Tested 2 g @ 10…500 Hz per IEC68-2-6

Agency certification

CENELEC

UL, C-UL

FM

INMETRO

IECEx

II (1) 2G Ex ib[ia] IIC T4
II (1) D [Ex iaD]
Class I, Groups A, B, C and D; Class II, Groups E, F and G;
Class III hazardous Locations.
Class I, Zone 1, AEx ib[ia] IIC T4.
Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.
Associated Apparatus with intrinsically safe
connections Class I, II, III, Div 1, Groups A--G
Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.
BR-Ex ia/ib IIB/IIC T4
[Zone 0] Ex ib[ia] IIC T4
[Ex iaD]

Certificate of conformity

CENELEC

UL, C-UL

FM

INMETRO

IECEx

DMT 98 ATEX 033 X
UL, C-UL File Number E197983
FM Certificate Number 3009806
05/UL-BRAE-0014X
IECEx BVS 09.0028X