Dcs 5000/automax installation verification – Rockwell Automation 61C613 16 Channel Analog Input Module User Manual

Page 14

Advertising
background image

3Ć2

Table 3.2Ć DCS 5000 Slot Configuration

Slot #

0

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15

2

2

2

2

2

2

2

2

2

2

2

2

2

2

base

address

(HEX)

Switch

- -

2

0

0

0

0

3

0

0

0

0

4

0

0

0

0

5

0

0

0

0

6

0

0

0

0

7

0

0

0

0

8

0

0

0

0

9

0

0

0

0

A

0

0

0

0

B

0

0

0

0

C

0

0

0

0

D

0

0

0

0

E

0

0

0

0

F

0

0

0

0

S1Ć1
S1Ć2
S1Ć3
S1Ć4
S1Ć5
S1Ć6
S1Ć7
S1Ć8

- -
- -
- -
- -
- -
- -
- -
- -

ăăăăăăăăăăD

ă=ăSwitch is closed

ăăăăăăăăăă-

ă=ăillegal slot

Step 4.

Insert the module into the desired slot in the rack. Use a

screwdriver to secure the module into the slot.

Step 5.

Attach the 50Ćpin flat cables to their mating halves on the

module. Attach the cables by aligning the triangle marks

on the cable end and the board socket. Make certain that

the connectors are the proper ones for this module. The

cable for channels 0Ć7 attaches to the middle connector.

The cable for channels 8Ć15 attaches to the lower

connector.

Step 6.

Turn on power to the rack.

Step 7.

Verify the installation. For DCS 5000/AutoMax, read the

section entitled DCS 5000/AutoMax Installation

Verification. For AutoMate, go on to the section entitled

AutoMate Installation Verification."

DCS 5000/AutoMax Installation
Verification

Verify the installation by connecting the programming terminal to the

system and running the ReSource Programming software. Note that

you will need the application program disk that came with the

ReSource Programming Software. Use the appropriate size disk for

your particular disk drive. Perform the following steps to verify the

installation of the module:
a. Edit the file SETUP613.BAS in the DCS subdirectory. Customize

the DATA statements beginning at statement 20000 to correctly

describe your configuration.

Advertising