Thermocouple Performance (14 bits)

ANSI Thermocouple Curve Conformance: + 0.2 deg F max
The following table details guaranteed accuracy and repeatability as compared to

National Bureau of Standards measurements using primary standards and ANSI

thermocouple curves. All sources of error have been included. The following

conditions apply:
1. Measurement is within 30 days of calibration.
2. Ambient temperature is 0Ć60 degrees C, draftĆfree and steady.
3. Common mode voltage = 0.

ANSI

Thermocouple

Type

Range

(degrees F)

Accuracy

(degrees F)

Range

(degrees C)

Accuracy

(degrees C)

E

J

K

T

B

R

-382 to 32

32 to 1832

-346 to 32

32 to 1400

-328 to 32

32 to 2500

-436 to 32

32 to 752

32 to 752

752 to 3308

32 to 3213

+ 2.9

+ 1.4

+ 1.7

+ 1.3

+ 3.2

+ 2.0

+ 3.7

+ 1.3

+ 20

+ 2.8

+ 2.8

-230 to 0

0 to 1000

-210 to 0

0 to 760

-200 to 0

0 to 1200

-260 to 0

0 to 400

0 to 400

400 to 1820

0 to 1768

+ 1.6

+ 0.8

+ 0.9

+ 0.7

+ 1.8

+ 1.1

+ 2.1

+ 0.7

+ 12

+ 1.6

+ 1.6