5Ć2

5.2

Bus Error

Problem: Error code 31" or 16" appears on the DCS 5000/AutoMax

processor module's LEDs, or register 3764 in the A30 or 15764 in the

A40 indicates a high bit in the corresponding slot. These errors

indicate there was a problem when the system attempted to access

the module. The possible causes of this error are a missing module,

amodule in the wrong slot, or amalfunctioning module. It is also

possible that the user is attempting to write to the wrong registers on

the module. Use the following procedure to isolate a bus error:
Step 1

Verify that the input module is in the correct slot.
Refer to section 4.4.1

Step 2

Verify that the rocker switches have been set correctly.
Refer to table 3.1 for the AutoMate 30/40 or 3.2 for DCS

5000/AutoMax for the correct settings of the address

switches.

Step 3

Verify that the application software has been written

correctly.
Verify that your application program is referencing the

proper module. Refer to the address that corresponds to

the switch settings in table 3.1 or 3.2.

Step 4

Verify that the module can be accessed.
Repeat step 7 in section 3.1. If the module now works you

have a programming problem. Review the examples that

have been provided. If the module does not work, there is

a hardware problem. Proceed to step 5.

Step 5

Verify that the hardware is working correctly.
One at a time, swap out the input module, the processor

module (s), and the backplane. After each swap, if the

problem has not been corrected, replace the original item

before swapping out the next item.