Rockwell Automation 61C613 16 Channel Analog Input Module User Manual

Page 19

Advertising
background image

4Ć3

4.2.2

Module Initialization

Whenever power is turned on to the rack or the module is reset, it is

necessary to initialize the module. Module initialization must follow

module reset or powerĆup. The initialization command contains the

following information:

Location (M+0)

0

Location (M+1)

0

Location (M+2)

0

0

0

0 rw 0

rw rw

Power line frequency

ą0 Ć 60 Hz

ą1 Ć 50 Hz

Temperature units for therĆ

mocouple readings

ą0 Ć Centigrade

ą1 Ć Fahrenheit

Data acquisition mode

ą0 Ć OnĆcommand

ą1 Ć Continuous

The power line frequency should be selected for maximum rejection

of power lineĆinduced noise.
The data acquisition mode specifies how the analog input channels

will be read, either onĆdemand (refer to section 4.2.10) or

continuously (refer to sections 4.2.7, 4.2.8, and 4.2.9).

4.2.3

Write Channel Number

The write channel number command sets a value into the module's

channel register pointer, which defines the A/D channel for

channelĆspecific commands. The write channel number command

contains the following information:

Location (M+0)

20

Location (M+1)

channel number

Location (M+2)

0

0

0

0

0

0

0

w

Auto increment switch
0 Ć Consecutive channelĆ

specific commands will not afĆ

fect the channel register

1 Ć The channel register will be inĆ

cremented after each channel

specific command

Valid channel numbers range from 0 to 15, corresponding to

channels 0Ć15.