Linear Performance (14 bits)

The following table details guaranteed accuracy and repeatability as compared to

National Bureau of Standards measurements using primary voltage standards. All

sources of error have been included. The following conditions apply:
1. Measurement is within 30 days of calibration.
2. Ambient temperature is 0Ć60 degrees C, draftĆfree and steady.
3. Common mode voltage = 0.

Range

Resolution

Absolute Accuracy

+12.50 mvolts

0.76

m

volts

+6

m

volts

+25.00 mvolts

1.53

m

volts

+8

m

volts

+50.00 mvolts

3.05

m

volts

+12

m

volts

+100.00 mvolts

6.10

m

volts

+24

m

volts

+1.25 volts

76.25

m

volts

+300

m

volts

+2.50 volts

152.5

m

volts

+600

m

volts

+5.00 volts

305.

m

volts

+1200

m

volts

+10.00 volts

610.

m

volts

+2400

m

volts