0 introduction – Rockwell Automation 61C613 16 Channel Analog Input Module User Manual

Page 7

Advertising
background image

1Ć1

1.0 INTRODUCTION

The 61C613 is an input module for the AutoMater 30/40 and DCS

5000/AutoMaxT. It features 16 individuallyĆisolated analog inputs

capable of multiplexing signals from any combination of

thermocouples and low or high level voltages, or RTDs. The module

must be used in conjunction with either the 61C614 Thermocouple/

Voltage Termination Panel, or the 61C615 RTD Termination Panel.
Two application programming disks are included with the input

module. Both disks contain exactly the same programs. The

programs allow you to verify the functionality of the module.The disks

also include sample programs for reading inputs using the module.
The module provides automatic linearization and cold junction

compensation for type B, E, J, K, R, and T thermocouples.

Thermocouples may be read in either degrees Centigrade or

Farenheit. Thermocouple inputs can be read as often as once every

110 msec. Thermocouple inputs require the use of the 61C614

Thermocouple/Voltage Termination Panel. The module can be used

to convert signals from RTDs, using the 61C615 RTD Termination

Panel. In this mode, the module must be configured for voltage

inputs, typically + 1.25 V.
The module provides offset and span compensation for voltage

inputs. Voltages can range from a full scale of +12.5 mvolts up to a

maximum of +10.0 volts. Voltages may be converted to either 12Ćbit

precision every 45 msec. or 14Ćbit precision every 75 msec. Voltage

inputs require the use of the 61C614 Termination panel.
This manual describes the functions and specifications of the input

module. It also includes a detailed overview of installation and

servicing procedures, as well as examples of programming methods.
Related publications that may be of interest:
D JĆ2605 AutoMate 30/40 PRODUCT SUMMARY
D JĆ3150 AutoMate 30/40 SOFTWARE INSTRUCTION MANUAL
D JĆ2611 DCS 5000 PRODUCT SUMMARY
D JĆ3675 DCS 5000 ENHANCED BASIC LANGUAGE

INSTRUCTION MANUAL

D JĆ3676 DCS 5000 CONTROL BLOCK LANGUAGE

INSTRUCTION MANUAL

D JĆ3630 RESOURCET AUTOMAXT PROGRAMMING

EXECUTIVE INSTRUCTION MANUAL

D JĆ3645Ć1 RTD TERMINATION PANEL INSTRUCTION MANUAL
D JĆ3646Ć1 THERMOCOUPLE/VOLTAGE TERMINATION PANEL

INSTRUCTION MANUAL

D IEEE 518 GUIDE FOR THE INSTALLATION OF ELECTRICAL

EQUIPMENT TO MINIMIZE ELECTRICAL NOISE

INPUTS TO CONTROLLERS FROM EXTERNAL

SOURCES

Advertising