0 diagnostics and troubleshooting, 1 incorrect data – Rockwell Automation 61C613 16 Channel Analog Input Module User Manual

Page 29

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections.

5.1

Incorrect Data

Problem: The data is either always off, always on, or different than

expected. When this happens the module is in the wrong slot or

malfunctioning, or there is a programming error. It is also possible

that the input is either not wired or wired to the wrong device. Use the

following procedure to isolate the problem:
Step 1

Verify that the input module is in the correct slot.
See section 4.4.1

Step 2

Verify that rocker switches have been set correctly.
Refer to table 3.1 for the AutoMate 30/40 or table 3.2 for

DCS 5000/AutoMax for the correct settings of the address

switches.

Step 3

Verify that the application software is written correctly.
Verify that your application program is referencing the

proper module. Refer to the address that corresponds to

the switch settings in table 3.1 or 3.2. Confirm that each

channel has been configured correctly.

Step 4

Verify that the module can be accessed.
Repeat step 7 in section 3.1. If the module now works you

have a programming problem. Review the examples that

have been provided. If the module does not work, there is

a hardware problem. Proceed to step 5.

Step 5

Verify that the input is wired to the correct device.
Confirm that all connections at the terminal strip are tight.

Refer to Appendix C for a definition of terminal strip

connections. Make certain that each input channel is wired

to the correct field device.
Make certain that the 50Ćpin flat cables are secure and

connected to the proper connectors on the module.
Connect a voltmeter to the proper points on the terminal

strip and confirm that the external device is generating the

correct voltage or current.
If you are using a 61C615 termination panel, measure the

external power supply to verify that it is producing +15

volts.

Step 6

Verify that the hardware is working correctly.
One at a time, swap out the input module, the termination

panel, the processor (s), and finally the backplane. After

each swap, if the problem has not been corrected, replace

the original item before swapping out the next item.

Advertising