2 electrical description – Rockwell Automation 61C544A RTD Module User Manual

Page 11

Advertising
background image

2Ć3

2.2

Electrical Description

The module provides sixteen channels of precise RTD temperature

information to AutoMax and AutoMate systems. Each channel

consists of a constant current source and a pair of high impedance

measurement inputs. See figure 2.2. The current sources are

powered by an onĆboard supply that is isolated from the system

common. No external userĆsupplied power supplies are required.

Thesixteen RTD inputs sharethesamecommon. This analog

common has 2500 VAC of isolation from thesystem common.
The sixteen pairs of measurement inputs are multiplexed to an

instrumentation amplifier which drives a fourteenĆbit A/D converter.

This configuration measures the voltage drop across the selected

RTD element.
The data register (registers 0 to 15) of a configured channel is

updated when the processor converts and averages channel input

samples over 16.6 ms for a 60 Hz line or 20 ms for a 50 Hz line. In

this manner, line frequency noise at the input of the A/D converter is

integrated out of the result that is provided to the system. This

overĆsampling of the analog inputs also simplifies the filter

requirements. A single pole analog filter is located on each

measurement input line.
The module also contains positive and zero references for A/D

converter calibration. These references are checked at the end of

each scan of the configured channels and the calibration coefficients

are updated accordingly. All nonĆzero references are derived from

the A/D converter's buriedĆzener reference. The reference for the

constant current sources is likewise derived from the A/D converter.

This provides a ratiometric style of conversion. No potentiometer

adjustments are required to maintain the specified accuracy.
The onĆboard processor averages the raw A/D converter data,

linearizes the average using the calibration coefficients, and then

performs a table lookĆup based upon the specified alpha value of the

RTD. This value will then either be written to the appropriate channel

data register (registers 0Ć15) or will become part of the running

average specified in register 26. The running average value is stored

in 0.1_C or 0.1_F units in the appropriate channel data register.
A broken wirefrom theRTD is indicated through an out of range

status bit in register 20. The module also provides high and low limit

registers which can be set by the user. Status registers then indicate

when the desired low/high values have been exceeded.
All read operations on the module's memory by the onĆboard

processor include a parity test. Failure of the parity test results in a

module shutdown. Processor modules can read all locations within

the slot address but can only write to registers 23 through 31.
The module will execute a full set of powerĆup diagnostics which

must executesuccessfully beforethemodulecan go into therun

mode.

Advertising