The following configuration task is intended as a guide to help you in defining

your systemĆwide RTD variables when using DCS 5000 and AutoMax version 2.1

and earlier. This task defines the common variables used in the sample

application task in section 4.4.
10 ! RTD Sample Configuration Task

20 ! April 22, 1991

30 !

100 TASK RTD[ TYPE=BASIC, PRIORITY=7, SLOT=0, CRITICAL=FALSE ]

110 !

220 IODEF VAT1_TEMP%[

SLOT=4, REGISTER=0 ]

230 IODEF VAT2_TEMP%[

SLOT=4, REGISTER=1 ]

240 IODEF VAT3_TEMP%[

SLOT=4, REGISTER=2 ]

245 !

300 IODEF VAT1_HH_ALARM@[

SLOT=4, REGISTER=16, BIT=0 ]

310 IODEF VAT1_H_ALARM@[

SLOT=4, REGISTER=17, BIT=0 ]

320 IODEF VAT1_L_ALARM@[

SLOT=4, REGISTER=18, BIT=0 ]

330 IODEF VAT1_LL_ALARM@[

SLOT=4, REGISTER=19, BIT=0 ]

340 !

400 IODEF VAT2_HH_ALARM@[

SLOT=4, REGISTER=16, BIT=1 ]

410 IODEF VAT2_H_ALARM@[

SLOT=4, REGISTER=17, BIT=1 ]

420 IODEF VAT2_L_ALARM@[

SLOT=4, REGISTER=18, BIT=1 ]

430 IODEF VAT2_LL_ALARM@[

SLOT=4, REGISTER=19, BIT=1 ]

440 !

500 IODEF VAT3_HH_ALARM@[

SLOT=4, REGISTER=16, BIT=2 ]

510 IODEF VAT3_H_ALARM@[

SLOT=4, REGISTER=17, BIT=2 ]

520 IODEF VAT3_L_ALARM@[

SLOT=4, REGISTER=18, BIT=2 ]

530 IODEF VAT3_LL_ALARM@[

SLOT=4, REGISTER=19, BIT=2 ]

540 !

590 IODEF CONF_AVE_SAMPLES% [

SLOT = 4, REGISTER = 26]

600 IODEF CONF_HH_ALARM%[

SLOT=4, REGISTER=27 ]

610 IODEF CONF_H_ALARM%[

SLOT=4, REGISTER=28 ]

620 IODEF CONF_L_ALARM%[

SLOT=4, REGISTER=29 ]

630 IODEF CONF_LL_ALARM%[

SLOT=4, REGISTER=30 ]

640 IODEF CONF_COMMAND%[

SLOT=4, REGISTER=31 ]

650 IODEF CONF_COMP@[

SLOT=4, REGISTER=22, BIT=15 ]

660 IODEF CONF_ERROR@[

SLOT=4, REGISTER=22, BIT=14 ]

670 IODEF CONF_CHAN_NUM%[

SLOT=4, REGISTER=23 ]

720 IODEF OUT_OF_RANGE%[

SLOT=4, REGISTER=20 ]

900 !

910 MEMDEF WARNING@

920 MEMDEF SHUTDOWN@