4.6

Restrictions on Use

The channels on the RTD module are to be configured from only one

application task.
Do not configure a channel on the RTD module unless an RTD is

connected to that channel. If you do, outĆofĆrange input values may

be generated.
If the RTD module is in an AutoMate remote rack, both the master

Remote I/O Processor and the slave Remote I/O Processor must be

M/N 45C201B or later. If either Processor is of an earlier version, the

remote rack will not stay onĆline with the master.
You can place up to 15 RTD modules in either a local or remote

AutoMate rack when using a 50 Amp AutoMate Power Supply