4Ć19

Register 3003= Reserved for future use.
Register 3004= Register contains the RTD channel's Number of

Samples. This value is provided by the data table in

the 5000Ćseries registers.

Register 3005= Register contains the RTD channel's High High

alarm value. This value is provided by the data table

in the 5000Ćseries registers.

Register 3006= Register contains the RTD channel's High alarm

value. This value is provided by the data table in the

5000Ćseries registers.

Register 3007= Register contains the RTD channel's Low alarm

value. This value is provided by the data table in the

5000Ćseries registers.

Register 3010= Register contains the RTD channel's Low Low alarm

value. This value is provided by the data table in

the 5000Ćseries registers.

Register 3011= Register contains the RTD channel's configuration

command. This value is provided by the data table

in the 5000Ćseries registers.

Registers 3100 to 3137= Registers contain the data read from the

RTD module.

Registers 5000 to 5027= Registers contain the data used to

configure the RTD channels. Each

channel uses six registers:

Not

# of

High

Low

Configure

Not

Used

# of

Samples

High

High

High Low

Low

Low

Configure

Command

Reg. 5000 = 0 0

20

2500

2000 1000 500

12288*

Reg. 5010 = 0 0

20

2500

2000 1000 500

12288ă

Reg. 5020 = 0 0

20

2500

2000 1000 500

12288ă

* 12288 = 3000 Hex

Note that you must use the POINT MONITOR function to enter these

values into the 5000Ćseries registers before you begin executing the

program.
Register 5200= Register contains the value (0) for the READY

command.