4.1.12

High Alarm Register (Register 28)

Register 28 defines the High alarm limit. If a channel's input value

exceeds this limit, the channel's corresponding bit in register 17 is set

to one. The value in register 28 is a 15Ćbit plus a signĆbit integer. This

value is in units of 0.1 degrees.
If register 28 does not contain an alarm value greater than the Low

alarm value, a configuration error will result. At powerĆup, the register

is set to a default value of 1000 (1000 x 0.1

o

C = 100

o

C).

4.1.13

Low Alarm Register (Register 29)

Register 29 defines the Low alarm limit. If a channel's input value is

less than this limit, the channel's corresponding bit in register 18 is

set to one. The value in register 29 is a 15Ćbit plus a signĆbit integer.

This value is in units of 0.1 degrees.
If register 29 does not contain an alarm value less than the High

alarm value, a configuration error will result. At powerĆup, the register

is set to a default value of -1000 (-1000 x 0.1

o

C = -100

o

C).

4.1.14

Low Low Alarm Register (Register 30)

Register 30 defines the Low Low alarm limit. If a channel's input value

is less than this limit, the channel's corresponding bit in register 19 is

set to one. The value in register 30 is a 15Ćbit plus a signĆbit integer.

This value is in units of 0.1 degrees.
If register 30 does not contain the lowest alarm value, a configuration

error will result. At powerĆup, the register is set to a default value of

-1500 (-1500 x 0.1

o

C = -150

o

C).