4.4

Sample DCS 5000/AutoMax

RTD Application Task

The sample DCS 5000/AutoMax RTD application task in figure 4.12 is

written for an RTD module in slot 4 which is connected to a 4Ćwire

RTD. In this example, three vats of solution are being monitored for

the following temperatures:
D High High Alarm = 250

o

C

D High Alarm = 200

o

C

D Low Alarm = 100

o

C

D Low Low Alarm = 50

o

C.

If you are using AutoMax version 2.1 or earlier, you would need to

define common (systemĆwide) variables in a configuration task

before writing an application task. The configuration task in Appendix

F defines the common variables in the sample task below.
If you are using DCS 5000/AutoMax version 3.0 or later, this

information would be entered in the configuration form using the

Programming Executive software.
Note that when RTD modules are placed in an AutoMax remote rack,

the powerĆup default values in registers 23 to 31 are reset to zero.

You must individually enter new values into these registers.