Rockwell Automation 61C544A RTD Module User Manual

Page 24

Advertising
background image

4Ć8

another configuration command. If you try to enter another

configuration command before bit 15 of register 22 is reset, error bits

7 and 14 in register 22 will be set.

4.1.9

Channel Number Register (Register 23)

Register 23 contains the number of the channel to be configured,

read, or reset. Channel numbers can range from 0 to 15. A channel

number outside of this range will be flagged as an error.

4.1.10

Number of Samples Register (Register 26)

Register 26 specifies the number of input data samples that will be

averaged together. The module maintains a running average of x"

number of input data samples. The value in the register is a 15Ćbit

plus a signĆbit integer. The default value is one. The maximum

allowable value is 60.
If the register contains a value of zero or one, no input data will be

averaged together. If the register contains a negative number, a

configuration error will result.
As the number of input samples increases, the time span of

averaging increases, which results in a less current input value for

use in the application program. See figure 4.9 for an equation to

determine the amount of time needed to calculate an average input

value for registers 0 to 15.

Where:
# of configured channels = 0 to 16
cycle frequency time =

20 msec for 50 Hz

16.6 msec for 60 Hz

system overhead = 5 msec
# of samples = 1 to 60
averaged time = time in seconds

= time the value in

reg. 0Ć15 was

averaged over

# of

configured

channels

cycle

frequency

time

system

overhead

# of

samples

*

+

*

Figure 4.9 Ć Equation for Determining the Input Value Averaging Time

4.1.11

High High Alarm Register (Register 27)

Register 27 defines the High High alarm limit. If a channel's input

value exceeds this limit, the channel's corresponding bit in register 16

is set to one. The value in register 27 is a 15Ćbit plus a signĆbit integer.

This value is in units of 0.1 degrees.
If register 27 does not contain the largest alarm value, a configuration

error will result. At powerĆup, the register is set to a default value of

4000 (4000 x 0.1_C = 400_C).