Rockwell Automation 61C544A RTD Module User Manual

Page 15

Advertising
background image

3Ć3

ÉÉ

Red

Black
White
Black

4ĆWire

RTD

3ĆWire

RTD

2ĆWire

RTD

Terminal Board

M/N 61C545 or

Field Wiring

500 Feet Max.

Belden 9502

1

2

4

6

8

10

12

14

16

V+
V-
Shield
Shield

V+
V-

V+
V-

I

O

I

R

I

O

I

R

I

O

I

R

Shield

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

15

18

20

M/N 61C546

Red

Black
White
Black
Red
Black
White
Black

Figure 3.2 Ć RTD Wiring Connections

Step 4.

Take the RTD module out of its shipping container. Take it

out of its antiĆstatic bag. Be careful not to touch the

connectors on the back of the module.

Step 5.

Insert the module into the desired slot in the rack. Use a

screwdriver to secure the module into the slot.

Step 6.

Attach the cables between the terminal board assemblies

and the module. Be sure that the DĆshell connectors are

oriented properly. Use a screwdriver to secure the DĆshell

connectors to the terminal board assemblies and the

module.

Step 7.

Turn on power to the system.

Step 8.

Connect the programming terminal to the system and run

the ReSource Programming Executive Software.
Stop all programs that may be running.
Configure the RTD channels you are using by following

the procedure in section 4.2. You cannot monitor the

registers on the module until you have configured the

channels. When you are done configuring, read the

channels' default values to verify that the installation is

correct. Refer to sections 4.1.1 to 4.1.15 for the default

values.