Rockwell Automation 61C544A RTD Module User Manual

Page 20

Advertising
background image

4Ć4

4.1.1

A/D Data Registers (Registers 0 to 15)

Registers 0 to 15 holdthe latest numeric data from RTD analog

channels 0 to 15. This data has been filtered (50 or 60 Hz filters) and

averagedtogether. See figure 4.1. The data is in a 15Ćbit plus a

signĆbit integer format. The data is displayed in units of 0.1 degrees

(either Celsius or Fahrenheit). If a channel is not configured, its data

is heldat zero.

Register 0 = A/D Data from Channel 0

Register 1 = A/D Data from Channel 1

Register 2 = A/D Data from Channel 2

S

S

S

Register 14 = A/D Data from Channel 14

Register 15 = A/D Data from Channel 15

Figure 4.1 Ć A/D Data Register Assignments

4.1.2

High High Alarm Status Register (Register 16)

Register 16 indicates the current status of each configured channel's

High High alarm. See figure 4.2. A bit is set in this register whenever

a channel's input value exceeds the configured High High alarm limit.

The bit is reset when the input value returns to a level below the

configuredlimit.

Register 16

Bits 0Ć15

Bit 0ă=ăChannel 0

Bit 5ă=ăChannel 5

Bit 10ă=ăChannel 10

Bit 1ă=ăChannel 1

Bit 6ă=ăChannel 6

Bit 11ă=ăChannel 11

Bit 2ă=ăChannel 2

Bit 7ă=ăChannel 7

Bit 12ă=ăChannel 12

Bit 3ă=ăChannel 3

Bit 8ă=ăChannel 8

Bit 13ă=ăChannel 13

Bit 4ă=ăChannel 4

Bit 9ă=ăChannel 9

Bit 14ă=ăChannel 14

Bit 15ă=ăChannel 15

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Figure 4.2 Ć High High Alarm Status Register