4Ć12
After you have placed valuesin registers26 through 30 and put the
write Configuration Command Code into register 31, the system
automatically transfersthe new channel parametersto the
appropriate locations in memory. To use these parameters on
another unconfigured channel, simply change the channel number
and put the write Configuration Command Code into register 31. If
you want to configure a channel with the original powerĆup default
values, you must first place the read Configuration Command Code
in register 31 to restore these values to registers 26 through 30. Note
that the channelson the RTD module must be configured from only
one application program.