4Ć12

After you have placed valuesin registers26 through 30 and put the

write Configuration Command Code into register 31, the system

automatically transfersthe new channel parametersto the

appropriate locations in memory. To use these parameters on

another unconfigured channel, simply change the channel number

and put the write Configuration Command Code into register 31. If

you want to configure a channel with the original powerĆup default

values, you must first place the read Configuration Command Code

in register 31 to restore these values to registers 26 through 30. Note

that the channelson the RTD module must be configured from only

one application program.