0 diagnostics and troubleshooting, 1 incorrect data – Rockwell Automation 61C544A RTD Module User Manual

Page 45

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections. Ifyou cannot correct the problem using the instructions

below, the module is not userĆserviceable. Ifthe procedure calls for a

component to be swapped with a replacement part and the problem

is not corrected, replace the original component and go on to the

next step.

5.1

Incorrect Data

Problem: The data is always on, always off, or different than

expected. The possible causes ofthis are a module in the wrong slot,

a programming error, or a malfunctioning module. It is also possible

that the RTD is either not wired or is wired incorrectly. Use the

following procedure to isolate the problem:
Step 1.

Connect the programming terminal to the system and run

the ReSource Programming Executive Software.

Determine whether the channel is configured by

examining register 21. Ifit is not, use the procedure in

section 4.2 to configure the channel.

Step 2.

For DCS 5000/AutoMax systems, verify that the module

configuration is correct. Verify that the RTD module is in

the correct slot.
Verify that the slot number being referenced agrees with

the slot number ofthe module.
For remote I/O installations, verify that the master slot and

remote drop numbers are defined correctly.

Step 3.

Verify that the field wiring is properly connected.

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN

SEVERE BODILY INJURY OR LOSS OF LIFE.

Turn off power to the module.
Confirm that all terminal board connections are tight.
Check the cables for continuity between the faceplate

connector and the terminal board assembly.
Turn on power to the module.

Step 4.

Check for an RTD out of range condition.
Monitor register 20. Use the MONITOR function in DCS

5000/AutoMax systems or the POINT MONITOR function

in AutoMate systems.

Advertising