Chapter

2

Installing the Monitor

Chapter Objectives

This chapter shows you how to install the monitor in a panel, rack, or
bench/tabletop and how to make monitor connections.

Review each mounting type and product dimensions before
installation.

Hazardous Locations

This equipment is suitable for the following hazardous locations
specified on the product nameplate:

Class I, Division 2 Groups A, B, C, D.

Class II, Division 2 Groups F, G.

Class III, Division 1.

nonhazardous locations.

The following statement applies to use in hazardous locations.

The monitors and ac adapters have an operating temperature code of
T4 when operating in a 50 °C (122 °F) ambient environment. Do not
install the terminals in environments where atmospheric gases have an
ignition temperature less than 135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for
hazardous locations.

Do not disconnect equipment unless power has been removed
and area is known to be nonhazardous.

Do not connect or disconnect components unless power has
been removed.

All wiring must comply with N.E.C articles 501-4(b), 502-4(b),
503-3(b) as appropriate.

Peripheral equipment must be suitable for the location in which
it is used.

All hazardous-location equipment must be mounted in an
enclosure that is suitably designed or rated for those specific
environmental conditions that will be present, and designed to
prevent personal injury resulting from accessibility to live parts.