Rockwell Automation SP120 AC Drive Demo Unit User Manual
Page 14

4-2
Using the SP200 AC Drive Demo Unit
Step 3. Press
or
until P-60 [
RESET
TO
DEFAULTS
] is
displayed.
Step 4. Press
to display the value of P-60 (0 should be
displayed).
Step 5. Press
to change the value to 1(Reset All Values
to Factory Defaults).
Step 6. Press
to accept the value.
The drive’s factory defaults have been restored.
Lab 1b: Setting up a basic drive configuration that uses
external I/O control.
Step 1. Press
until the
PROGRAM
LED
turns on to enter
program mode.
Step 2. Press
or
until P-00 [
MINIMUM
SPEED
] is
displayed.
Step 3. Press
to display the value of P-00.
Step 4. Press
or
until the value 5 is displayed. This
sets the minimum speed to 5 Hz.
Step 5. Press
to accept the value.
Step 6. Press
until P-01 [
MAXIMUM
SPEED
] is displayed.
Step 7. Press
to display the value of P-01.
Step 8. Press
or
to change the value to 60, if
necessary.
Step 9. Press
to accept the displayed value.
Step 10. Repeat this process for all of the parameters listed
in table 4.2. The parameter settings are based on
the demo unit’s motor nameplate data listed below.
Note that the demo unit contains a Model C SP200 drive.
• 1600 RPM
• .22 A FLA
• 60 Hz
PR OG