Rockwell Automation SP120 AC Drive Demo Unit User Manual

Page 21

Advertising
background image

Running the Demo Unit

4-9

Step 7. Press

, if necessary, until d-01 [

COMMAND

FREQUENCY

] is displayed.

Step 8. Turn the

STOP

/

RUN

switch to

STOP

. Notice that the

output frequency immediately drops to 0. Notice
how long it takes the motor to stop.

Lab 4b: Programming the drive for a ramp-to-rest stop.

Step 1. Press

to enter program mode.

Step 2. Set P-34 to 0 (Ramp-to-Rest).

Step 3. Press

to enter display mode.

Step 4. Press

, if necessary, until the value of d-01

[

COMMAND

FREQUENCY

] is displayed.

Step 5. Turn the

STOP

/

RUN

switch to

RUN

.

ANALOG

CHAN

#1

should be turned fully clockwise. Wait for the drive
to reach full speed.

Step 6. Turn the

STOP

/

RUN

switch to

STOP

. Notice that the

output frequency and voltage decreases over time
(ramps down) to zero.

Lab 4c: Programming the drive for DC injection braking.

DC injection braking is a stopping method whereby DC
current is applied to a single winding in a motor.

Step 1. Set P-34 to 2 (DC Injection).

Step 2. Set P-35 [

DC

BRAKE

CURRENT

] to 100. This specifies

the output current level in percent.

Step 3. Set P-36 [

DC

BRAKE

TIME

AT

STOP

] to 3.0. This sets

the amount of time in seconds that the current
specified in P-35 is applied to the motor. The DC
injection begins when the drive is commanded to
stop.

Step 4. Press

to enter display mode.

Step 5. Press

, if necessary, until the value of d-01

[

COMMAND

FREQUENCY

] is displayed.

Step 6. Turn the

STOP

/

RUN

switch to

RUN

.

ANALOG

CHAN

#1

should be turned fully clockwise. Wait for the drive
to reach full speed.

PR OG

PR OG

PR OG