Running the Demo Unit

4-5

A configured output is an output that can be programmed to
indicate various conditions. On the demo unit, the red

CONF

OUT

indicator lamp is hardwired to the configurable output

terminals on the drive’s terminal strip (terminals 11 and 12).

In this lab, you will program the configured input as a function
loss interlock and as a reversing switch. You will program the
configured output to indicate various conditions.

Before proceeding with this lab, do the following:

Step 1. Be sure the drive is stopped and the

STOP

/

RUN

switch is in the

STOP

position.

Step 2. Verify that P-10 [

START

CONTROL

] is set to 2. This

will set the start control to 2-wire control.

To set P-10, use the following procedure:

a. Press

until the

PROGRAM

LED

turns on.

b. Press

or

until P-10 is displayed.

c. Press

to display the value of P-10.

d. Press

or

until 2 is displayed.

e. Press

to accept the value.

Lab 3a: Programming the input as a function loss
interlock.

A function loss is a hardwired input to the drive that can act
as an interlock from some other equipment. If that other
equipment fails or stop operating, this will cause a Function
Loss fault in the drive (fault code FL is displayed). This fault
will keep the drive from starting or will stop the drive if it is
operating.

The switch labeled

CONF

IN

is wired as the configured input.

Step 1. Verify that the

CONF

IN

switch is in the 1 position.

Step 2. Verify that the

STOP

/

RUN

switch is in the

STOP

position.

Step 3. Set P-11 [

CONFIGURABLE

INPUT

] to 0 (Function Loss).

PR OG