Running the Demo Unit

4-10

Step 7. Turn the

STOP

/

RUN

switch to

STOP

. Notice that the

output frequency and voltage dropped to 0
immediately.

Step 8. Reset the following parameters:

P-34 to 1
P-35 to 10
P-36 to 0.0

Lab 5: Setting up an avoidance frequency.

Tools required: None

Avoidance frequency parameters are used to prevent the
drive from continuous operation within a range (band) of
frequencies.

Step 1. Set P-37 [

AVOIDANCE

FREQUENCY

] to 30.0 Hz. This

specifies the midpoint of the band.

Step 2. Set P-38 [

AVOIDANCE

FREQUENCY

BAND

] to 20.0 Hz.

This sets the width of the band. In this case, the
width of the band is set from 20.0 Hz to 40.0 Hz.

Step 3. Turn the speed pot to zero (

ANALOG

CHAN

#1 should

be turned fully counter-clockwise).

Step 4. Press

to enter display mode. Press

, if

necessary, until the value of d-01 [

COMMAND

FREQUENCY

] is displayed.

Step 5. Turn the

STOP

/

RUN

switch to

RUN

.

Step 6. Slowly turn the speed pot clockwise, and watch the

display.

Notice that the motor holds up at 20.0 Hz and

speeds up at 40.0 Hz.

Step 7. Press

until d-00

[

COMMAND

FREQUENCY

] is

displayed.

Step 8. Turn the speed pot to zero, and then slowly turn the

speed pot up and down.

Notice when the motor increases in speed, holds

speed, and decreases speed.

Step 9. Reset the following parameters:

P-37 to 0
P-38 to 0

Step 10. Turn the

RUN

/

STOP

switch to

STOP

.

PR OG