Running the Demo Unit

4-8

Step 11. Set P-13 [

CONFIGURABLE

OUTPUT

LEVEL

] to 30.0.

This sets the level at which the output will turn on to
30.0 Hz.

Step 12. Turn the speed pot (

ANALOG

CHAN

#1) fully

clockwise. The red indicator lamp should be on.

Step 13. Press

to enter display mode.

Step 14. Press

until d-01 [

OUTPUT

FREQUENCY

] is

displayed.

Step 15. Slowly turn the speed pot counter-clockwise. Notice

that the red indicator lamp turns off when the
frequency drops below 30.0 Hz.

Step 16. Set the s

TOP

/

RUN

switch to

STOP

.

Lab 4: Programming various stopping methods.

Tools required: None

This lab consists of three parts:

a. Programming the drive for a coast-to-rest stop.

b. Programming the drive for a ramp-to-rest stop.

c. Programming the drive for DC injection braking.

Lab 4a: Programming the drive for a coast-to-rest stop.

Step 1. Press

until the

PROGRAM

LED

turns on to enter

programming mode.

Step 2. Press

or

until P-34 [

STOP

CONTROL

] is

displayed.

Step 3. Press

to display the value of P-34.

Note: The drive may be at the default value of 0

(Ramp-to-Rest), which means the output voltage
and frequency is lowered based on the decel time.
During the previous labs, you may have noticed
how quickly the drive stopped.

Step 4. Set P-34 to 1 (Coast-to-Rest).

Step 5. Turn the

STOP

/

RUN

switch to

RUN

and turn the speed

pot (

ANALOG

CHAN

#1) fully clockwise.

Step 6. Press

to enter display mode.

PR OG

PR OG

PR OG