Rockwell Automation SP120 AC Drive Demo Unit User Manual

Page 18

Advertising
background image

Running the Demo Unit

4-6

Step 4. Turn the

STOP

/

RUN

switch to

RUN

. The motor should

rotate to the commanded speed selected on the
speed pot (

ANALOG

CHAN

#1).

Step 5. Turn the

CONF

IN

switch from 1 to 0. Note the

following things that occur:

• The drive faults, and the motor coasts to a stop.

• The drive displays the fault code FL (Function

Loss).

• The drive status

LED

changes from green (OK) to

red (problem exists).

• The

RUN

and

PROGRAM

LED

s turn off.

Step 6. Turn the

CONF

IN

switch back to 1, and turn the

STOP

/

RUN

switch back to

STOP

. Notice that nothing

happens because the fault condition prohibits the
drive from running.

Step 7. Press

to reset the fault and note the following:

• The FL fault code is not displayed.

• The drive status

LED

changes from red to green.

Lab 3b: Programming the input as a reversing switch.

Step 1. Set P-11 [

CONFIGURABLE

INPUT

] to 1. This programs

the drive to run in the opposite direction when the
configurable input is on.

Step 2. Verify that the

STOP

/

RUN

switch is in the

STOP

position and that the

CONF

IN

switch is in the 0

position.

Step 3. Turn the

STOP

/

RUN

switch to

RUN

, and notice the

direction of motor rotation. Turn the

STOP

/

RUN

switch

to

STOP

to stop the drive.

Step 4. Turn the

CONF

IN

switch to 1, and notice that the

direction of motor rotation is reversed. Turn the

CONF

IN

switch to 0 to stop the drive.

Important: If you set the

STOP

/

RUN

SWITCH

to

RUN

while the

CONF

IN

switch is set to 1, or vice versa, a drive

fault will occur and CF will be displayed. The
drive stops if more than one input (forward,
reverse, or jog) is on.