Running the Demo Unit

4-7

If this fault occurs, turn the

STOP

/

RUN

switch to

STOP

and the

CONF

IN

switch to 0. Then press

to reset the fault.

Lab 3c: Programming the configurable output.

The red indicator lamp (

CONF

OUT

) on the demo unit is

hardwired to the configurable output on the terminal strip
(terminals 11 and 12).

Step 1. Set P-12 [

CONFIGURABLE

OUTPUT

] to 0 (No Fault).

This programs the output to turn on when the drive
is not faulted.

Step 2. Turn the

STOP

/

RUN

switch to

RUN

. (The motor should

rotate).

Step 3. Turn the

CONF

IN

switch to 1. Notice the drive now

displays a CF fault code. Also note that the red
indicator lamp is off.

Step 4. Turn the

CONF

IN

switch to 0, and the

RUN

/

STOP

switch to

STOP

.

Step 5. Press

to reset the fault. Notice that the CF

code on the display is gone, and the red indicator
lamp is now on.

Step 6. Set P-12 to 2 (Running). This programs the output

to turn on when the drive is commanded to run.

Step 7. Turn the

STOP

/

RUN

switch to

RUN

, then back to

STOP

.

Turn the

CONF

IN

switch to 1, then back to 0. Notice

when the red indicator lamp turns on and off.

Step 8. Set P-12 to 3 (At Frequency). This programs the

configured output to turn on when the output from
the drive equals the speed set by the speed
reference pot,

ANALOG

CHAN

#1 (commanded

frequency speed).

Step 9. Turn the

STOP

/

RUN

switch to

RUN

. Notice that the red

indicator lamp does not turn on immediately, but
remains off until the output is equal to the speed
reference. Rotate the speed pot clockwise and
counter-clockwise and watch the red indicator lamp.

Step 10. Set P-12 to 4 (Above Frequency). This programs

the configured output to turn on when the drive
exceeds a specified frequency.