Rockwell Automation Publication GMSI10-UM002D-EN-E - August 2012

269

Run Up/Coast Down Application

Chapter 10

Spacing

Controls the spacing between collected spectra.
Delta RPM- A fixed speed change between spectra.
% Delta RPM- A percentage speed change between spectra.
Delta Time- A fixed time interval between spectra.
Delta RPM+Delta Time- A combination of speed and time interval

settings. If speed stops changing then spectra are calculated using
the Time Interval value.

% Delta RPM+Delta Time- A combination of speed and time

interval settings. If speed stops changing then spectra are
calculated using the Time Interval value.

Options:
Delta RPM
% Delta RPM
Delta Time
Delta RPM+Delta Time
% Delta RPM+Delta Time
Important: Your selection affects the Speed
Interval and Time Interval settings.

Speed Interval (RPM)

Sets the speed interval used in calculating FFT spectra.

1…240 RPM or % RPM
This parameter not used when Spacing is set to
`Delta Time.‘

Time Interval (sec)

Sets the time interval used in calculating FFT spectra.

.001…604800 seconds
This parameter is not used when Spacing is set to
‘Delta RPM‘ and ‘% Delta RPM.‘

Display Units

Sets the Y-axis units.

The available units depends on the transducer
used to collect data.

See Table 44 on page 258

.

LF Cutoff

Determines whether to apply a low frequency filter (0.3 times the
running speed) to the data.

Options:
Off
On

Detection

Sets the signal detection and scaling display for the table.
Peak - Measured RMS value multiplied by the square root of two

(1.4142).

Pk-Pk - Measured RMS value multiplied by two times the square

root of two (2.8284).

RMS - Root mean squared signal level of the input signal.

Options:
RMS
Peak
PkPk

Num Traces

Sets the number of traces or order tracks to be displayed in the table.

Options:
1
2
Note: Your selection determines the available
number of Trace Order parameters.

Trace Order #1-#4

The order numbers to be tracked and displayed in the table.

.001…166 orders
This value cannot exceed the Max No Orders value
set in the RUCD Setup screen.

See Table 44 on page 258

.