Rockwell Automation Publication GMSI10-IN001A-EN-P - May 2013

8 Enwatch Unit

Wire the Enwatch Unit

For optimum performance, use shielded cables for all connections to the Enwatch
unit. For sensors such as accelerometers, connect the screens on the cables to
chassis ground at only one point. The optimal place for this is inside the Enwatch
enclosure and eight ground terminals are provided for this purpose. Connect the
screen at only one end; do not connect to ground at both ends.

Analog Input Configuration

Each channel (16 total) has a 3-way header associated with it. These are labeled
with the channel number and ‘A’ or ‘B’. The three jumper options and couplings
are the following.

Coupling

Fitted to Position

Description

ICP

x A

(1)

(1) Where x is the channel number, 1-16.

ICP power (nominal 24 V at 3.6 mA constant current for
transducer powering)

DC

x B

(1)

DC coupled

AC

Not Fitted

AC coupled

IMPORTANT

The -3dB point of the high-pass coupling for the ICP interface and AC Coupled

configuration is 0.07 Hz.

Earth Ground Terminal Strip

Mains Power Input and
Earth Ground Terminals