Trigger isolation jumpers – Rockwell Automation EK-44750C Enwatch Unit User Manual

Page 9

Advertising
background image

Rockwell Automation Publication GMSI10-IN001A-EN-P - May 2013

Enwatch Unit 9

Trigger Isolation Jumpers

These jumpers cause the four trigger inputs to be isolated or non-isolated.
Non-isolated means the common of the trigger input can be connected to the
common of the Enwatch unit. With a jumper removed, the trigger is isolated.
The following table describes the jumper positions.

Mode

Jumper Position

External trigger 1 isolated

17 Out

External trigger 1 non-isolated

17 In

External trigger 2 isolated

18 Out

External trigger 2 non-isolated

18 In

External trigger 3 isolated

19 Out

External trigger 3 non-isolated

19 In

External trigger 4 isolated

20 Out

External trigger 4 non-isolated

20 In

IMPORTANT

If an external sensor is powered from pin 1 of the external trigger terminals, the
jumper corresponding to the trigger channel must be inserted to provide a ground
return path for the sensor power.