C

HAPTER

2

Install and Wire the Drive

2-1

Install and Wire the Drive

ATTENTION: .The user is responsible for conforming to all other applicable
standards. Wiring practices, grounding, disconnects, and overcurrent protection are
of particular importance. Size and install all wiring in conformance with the
applicable standards. Failure to observe this precaution could result in severe
bodily injury or loss of life.

ATTENTION: .This equipment must be connected to a power source for which it
was designed. Compare available power with the requirements listed on the
nameplate to insure that voltage, frequency, phase, current capacity and
interrupting capacity are adequate.
Failure to observe this precaution could result in severe bodily injury or loss of life.

2.0

Recommended AC Line and DC Armature Fuses

The user must select the correct fuse type (ultra fast, semiconductor protection) for drive AC
line and DC armature fuses from the table 5.4 in chapter 5. The armature fuse is only for four
quadrant drives (S-6R).

2.1

Install the Drive

Install the drive(s) in the cabinet. Refer to figures 2.1 to 2.6 for mounting dimensions.

Minimum clearances of 100 mm must be maintained when the drive is mounted within a
cabinet. This allows adequate ventilation for the drive.

The user must ensure that the drive's ambient temperature specification is met.
For more information refer to page 1 of Appendix A.