Troubleshooting/Diagnostics

4-9

Table 4.2 - Alarm Codes (Continued)

CODE

DISPLAY

DESCRIPTION

A00032

SUSTAINED SPEED

Motor speed did not fall below

STOP SPEED THRESHOLD (P.113)

in the

required amount of time during a stop (this time is automatically set to
two times the

DECELERATION RATE

(P.002)

time).

Possible causes:

DECELERATION RATE

(P.002)

not set properly.

STOP SPEED THRESHOLD

(P.113)

not set properly.

Overhauling load maintaining motor speed higher than the

STOP

SPEED

THRESHOLD

.

Incorrect speed/voltage feedback scaling.

A00033

SUSTAINED
ARMATURE
CURRENT

Armature current was unable to reach discontinuous conduction while
stopping the drive.
Possible causes:

Motor CEMF too high or line voltage too low for proper commutation.

A00050

CML FEEDBACK
SCALING ERROR

Armature current feedback could not be scaled properly based on the
values entered for

MOTOR RATED ARM AMPS

and

MAXIMUM CURRENT

.

Verify that these parameter values are correct for your application.
Verify that

CT TURNS RATIO

has been set to the correct value for your

drive (see parameter description).

A00051

LOW MINIMUM
SPEED

The MINIMUM SPEED value is less than 10% of the MAXIMUM
SPEED value. This alarm will not be triggered on power-up. It only
occurs when maximum or minimum speed has changed.
Verify that these parameter values are correct for your application.

A00052 (no message)

NEG CUR LIM INV EN

(P.226)

has changed state, either enabling or

disabling the negative current limit inverters. The parameters

POS

CURRENT LIMIT SEL

(P.223)

and

NEG CURRENT LIMIT SEL

(P.224)

have

been set to

REGISTER

- Carefully check your current limit scheme and

the values of

POSITIVE CURRENT LIM

(P.005) and

NEGATIVE CURRENT LIM

(P.006) to avoid unintended drive operation.

A00700

RETENTIVE
MEMORY SAVE
ERROR

An attempt to save information (parameter values, fault log data or the
keypad reverence value) to retentive memory failed. The drive may
continue to be operated.
Possible cause:

Regulator board failure.