Technical Specifications

A-3

Regulation (with 95% load change):

Table A.2 - Tachometer Speed Regulation

Regulation Arrangement

Speed Change with
95% Load Change

Speed Change from
All other Variables

Part Number

Armature Voltage Regulation
with IR Comp.

2-3 %

15%

Not applicable.

Closed Loop

with Analog tach

1%

2%

-

with Pulse tach 1)

0.01%

0.01%

762.70.00

1) Optional Pulse Tachometer Feedback kit required (See instruction manual 49’1343).

Speed Range:

Operator's Speed Adjustment ............................................................................. 0 to rated speed

Specification Speed Range ................................100:1 based on Gear In Speed and tachometer

Drive Efficiency:

Drive Only ...................................................................................... 98.6% (rated load and speed)

Drive and Motor ..........................................................................................................85% typical

Displacement Power Factor, Power Loss Pv and Output Current:

Power Factor: 88% typical (rated load & speed, decreasing linearly with speed)
Typical percent speed depends on motor operating speed and motor frame size.
Power Consumption at no load: see P

A

in Table A.3.

Table A.3 - Drive Specifications

Unit-Type

I

ad

I

anom

I

amax

I

F

P

A

P

v

(at I

a nom

)

25 A

25 A

20 A

30 A

4 A

60 VA

120 W

60 A

60 A

50 A

75 A

4 A

60 VA

210 W

150 A

150 A

125 A

187 A

10 A

85 VA

460 W

250 A

250 A

208 A

312 A

10 A

90 VA

715 W

450 A

450 A

375 A

562 A

10 A

90 VA

1215 W

800 A

800 A

667 A

1000 A

12 A

120 VA

2120 W

1200 A, 500V

1200 A

1000 A

1500 A

15 A *

400 VA

2680 W

1600 A, 500V

1600 A

1334 A

2000 A

15 A *

400 VA

3750 W

2000 A, 500V

2000 A

1667 A

2500 A

15 A *

400 VA

4600 W

1600 A, 575V

1600 A

1334 A

2000 A

15 A *

400 VA

3900 W

1600 A, 690V

1600 A

1334 A

2000 A

15 A *

400 VA

4100 W

I

ad

= Maximum continuous current without overload capability (I

ad

= 1.2 x I

a nom

)

I

a nom

= Nominal continuous current with overload capability 50% during 1 minute

every 10 minutes

I

a max

= Maximum current during 1 minute after 9 minutes operation with Ia nom

(I

a max

= 1.5 x I

a nom

)

I

F

= Field current without overload capability

* A maximum field current of 20 A is permitted, if the power unit blower is switched on

together with the motor field.