Drive Setup and Adjustment

3-5

The expected analog tachometer voltage range can be set to a maximum of 250 or 62 VDC.
J11 selects the hardware circuitry to maximize the resolution over the entire speed range.

Jumper J14

Jumper J11

Gear In Speed Tach Volts < 16 volts

LOW

16

Gear In Speed Tach Volts < 31 volts

LOW

31/125

Gear In Speed Tach Volts < 62 volts

LOW

62/250

Gear In Speed Tach Volts < 125 volts

HIGH

31/125

Gear In Speed Tach Volts < 250 volts

HIGH

62/250

Note that the output voltage of the tachometer must not exceed 250 VDC when the motor is
rotating at GEAR IN SPEED. To calculate the output voltage, multiply the two parameter
values:
Tach Voltage at GEAR IN SPEED = GEAR IN SPEED x ANALOG TACH VOLTS

1000

1000

3.4.7

Set the Line Speed Reference - Jumpers J12 and J10

The AUTO REF Jumpers J12 and J10 select the type of Line Speed reference. J12 selects the
type of signal - VOLTS (Voltage) or MAMPS (milli-amps). J10 selects the range.

+ / - 10 VOLTS MAX

4 - 20 mA

10 - 50 mA

J12

J10

J12

J10

J12

J10

!

VOLTS

10 - 50

!

!

VOLTS

!

VOLTS

10 - 50

!

!

VOLTS

!

VOLTS

10 - 50

!

!

VOLTS

!

(BOTH)

!

!

4 - 20

!

(BOTH)

!

!

4 - 20

!

(BOTH)

!

!

4 - 20

!

MAMPS

PARK

!

!

!

MAMPS

PARK

!

!

!

MAMPS

PARK

!

!

Figure 3.2 - AUTO REF Jumpers (J12 and J10)

3.4.8

Scale the Armature Current Feedback - Jumper J18

ATTENTION: The drive will not run at the correct speed if this jumper is not set to
the correct position. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

The ARM I FB RB Jumper J18 scales the armature current feedback signal. The drive
calculates the value of the burden resistor needed to scale the armature current feedback
signal. The calculations are based on the values of MOTOR RATED ARM AMPS (P.008) and
MAXIMUM CURRENT (P.007).
The OIM displays the correct position of this jumper during the Quick Start procedure.
Verify this setting before performing the Self-Tuning procedure.

3.4.9

Inspect Jumper J26

This jumper determines whether or not a fault is generated when a tacho loss occurs or the
armature is open.

ATTENTION: Jumper J26 is for factory personnel use only. The user must not
change the status of this jumper. Misapplication of this jumper can cause the motor
to run at dangerously high speeds. Failure to observe this precaution could result in
bodily injury or loss of life.

J26 is intended for use by Rockwell Automation factory personnel only. Verify that it is set as
listed in table 3.1.