Drive Setup and Adjustment

3-3

3.4.1

Set the Regulator Type Jumper J15

ATTENTION: The J15 jumper must be set to the TORQUE/CURRENT position
when using the WebPak 3000 drive’s feature to “switch-on-the-fly” from speed/
voltage control to torque/current control. Applying a drive as a direct current
regulator has safety issues that must be considered. Refer to the WebPak 3000
Software Reference (D2-3444) for proper setup of this function. Failure to observe
these precautions could result in severe bodily injury or loss of life.

J15 determines whether the drive uses Speed/Voltage or Torque/Current regulation.

J15 must be set to CURRENT in order to be able to switch from a speed regulator to a current
regulator over the network.

When CURRENT is selected, only the terminal strip or a Communication Board can be used as
the control source.

Also note that speed/voltage parameters must be set to provide overspeed protection for the
drive.