Technical Specifications

A-5

Analog Tachometer Feedback

Tach Voltage at Gear-in Speed .................................................................... 10 - 250 V DC

NOTE: J14 Jumper position and connection of DC-Tachometer must correspond.

Jumper J14

Jumper J11

Gear-in Speed Tach Volts

< 16 V

LOW

16

< 31 V

LOW

31/125

< 62 V

LOW

62/250

< 125 V

HI

31/125

< 250 V

HI

62/250

Analog Outputs:

The two metering analog outputs are available at regulator board terminals 24, 25 and 26.
Terminal 25 is the common connection for both output signals. The selected signals for both
meter outputs are averaged (filtered) over 100 msec to reduce meter fluctuations.
METER OUT 1 SELECT (P.404) corresponds to terminals 24 and 25 (default: CML
FEEDBACK). METER OUT 2 SELECT (P.405) corresponds to terminals 25 and 26 (default:
SPD LOOP FEEDBACK).
Refer to Appendix B, METER OUT 1 SELECT (P.404) and METER OUT 2 SELECT (P.405)
parameters, for additional drive test points that can be configured to source Meter Outputs 1
and 2.

Electrical Specifications:

Output Voltage..................................................................................................+/- 10 V DC

Maximum Load 4 milliamps

Drive Current Transformer Turns Ratio

Unit-Type

Tp/Tn

25 A

208

60 A

416

150 A

833

250 A

2000

450 A

3000

800 A

5230

1200 A,

8000

1600 - 2000 A

10500