Rockwell Automation WebPak 3000  DC Drives Hardware Reference, Installation and Troubleshooting User Manual

Page 32

Advertising
background image

2-20

WebPak 3000 DC Drive Hardware Reference

Table 2.5 - I/O Expansion Analog Inputs

Parameter Name

Parameter Number

Terminal Strip Location

TENSION SETPOINT IN

P.492

50, 51

TENSION/DANCER FDBK

P.493

52, 53

TENSION SETPT SIG TYPE

P.413

TENSION SETPOINT ZERO

P.414

TENSION SETPOINT GAIN

P.415

TENSION/DANCER ZERO

P.416

TENSION/DANCER GAIN

P.417

* Terminals 33 (+10 VDC) and 34 (GND) are available for use with up to two 5 k

potentiometers.

Analog Outputs

The I/O Expansion board supports two analog outputs. Analog output 2 can generate a bipolar
DC voltage only. The other can be configured to generate one of the following signals: DC
voltage (0 to

±

10 VDC) or 4-20 mA. Both outputs are unfiltered (whereas standard meter

outputs are averaged). Analog outputs can be scaled to generate DC voltage signals as low as
5 V, but maximum resolution (0.025%) is obtained when the full scale output signal is used.
The full scale value is determined based on the selected parameter group: load, speed,
voltage, power, field, or other. Analog output signals are updated every I/O scan (typically 20
msec). Table 2.6 lists the analog outputs and related parameters. Figure 2.9 provides an
example of how to wire an external supply for 4-20 mA output.

Table 2.6 - I/O Expansion Analog Outputs

Parameter Name

Parameter Number

Terminal Strip Location

ANLG OUT 3 SELECT

P.418

54, 55

ANLG OUT 3 SIG TYPE

P.419

ANLG OUT 3 GAIN ADJ

P.420

ANLG OUT 4 SELECT

P.421

56, 57

ANLG OUT 4 GAIN ADJ

P.422

Frequency Input

The I/O Expansion board supports one unipolar frequency input: FREQ IN (P.491). The freq.
input signal is read every 20 msec. Table 2.7 lists the frequency input and related parameters.

Table 2.7 - I/O Expansion Frequency Input

Parameter Name

Parameter Number

Terminal Strip Location

FREQ IN

P.491

39, 40, 41

FREQ IN ZERO

P.423

FREQ IN FULL SCALE

P.424

Frequency Output

The I/O Expansion board supports one unipolar frequency output. The output is unfiltered.
The full scale value is determined based on the selected parameter group: load, speed,
voltage, power, field, or other. The frequency output signal is updated every 20 msec.
Table 2.8 lists the frequency output and related parameters.

Table 2.8 - I/O Expansion Frequency Output

Parameter Name

Parameter Number

Terminal Strip Location

FREQ OUT SELECT

P.425

42, 43, 44

FREQ OUT ZERO

P.426

FREQ OUT FULL SCALE

P.427